Home > PRODUCTS > LAB AIR CONDITIONING > With hydronic module > MED Branca Idealair

MED Branca Idealair

room air volume to be conditioned: (100 - 300) m3

climatic units with HFO refrigerants (GWP lower than 1) with hydronic module

Overview

ASK FOR A QUOTATION:

climatic-unit-type-med
Model:  
MED + Hydronic
Type MED only
climatico climatic Klima klimaticheskiy
termostatico thermostatic termostaticheskiy
Mappatura Mapping laboratornoye kartirovaniye
Ispezione Inspection osmotr
Tecnico Technician tekhnicheskiy
Spare parts

The climatic unit model MED Branca Idealiar maintains temperature ( C / F) and relative humidity (%) within close tolerances for ambient volumes up to 300 m3


air-flow-distribution hydronic-module

Here are some of the advanced features of the climatic unit:

  • Wide operating range with atmospheric conditions from -20 to 40 C and relative humidity from 10% to 90%;
  • Electrical compatibility according to CE, UL and CSA certification requirements;
  • Modular distribution system with tangential diffusion and air intake at speeds lower than 0.15 m / s on the work surface;
  • Cooling circuit lamination through electronic modulating valves and refrigerated water circulating devices;
  • Reverse osmosis water purification system for the production of demineralized water at 0 F;
  • Evaporative system with humidification device and fine regulation heating elements;
  • Indoor fan with coaxial transmission and electronic control as required by EU standards;
  • Prefiltration frontal or from air ducts G3-G4;
  • HMI Touch 7" and PLC for user interface, value monitoring and graphic trend display and supervision system compatibility;
  • Technical remote support;
  • Reading resolution of probes at +/- 0.01 C or % on F.S .;
  • Diagnostics and alarm statistics
  • Integrated datalogging
  • NORMAL / ECO weekly programming
  • Manual and guidelines for the use of the Climatic Element
Specifications
ModelMED
Ambient volume:(100-300) m3
Heating:9 KW
Cooling:7 KW
Humidification:4,5 KW
Refrigerant:R1270/ HFO R1234ze R1234ze
Ventilation:1,6 KW
Air flow:3000 m3/h
Fan transmission:Coaxial
Air exchange:1 volume/h
Control ranges:C 10 ..... 30
% 40 ..... 80
Water charge pipe:3/4"
Water discharge pipe:3/4"
Water discharge connection:3/4"
Cooled water pipe section:20 mm
GWP:< 1
Lubrificant:POE, PAG
Power supply:Three-phase (3ph+N+PE)
Dimensions:130x60x190
Net weight:400 Kg
Photogallery