Home > PRODUCTS > PRECISION AIR CONDITIONING > Cooled water > MAC Branca Idealair -->

MAC Branca Idealair

Designed to manage stable conditions for big air volumes up to 800 m3

Precision chilled water climatic unit

Overview:

REQUEST A QUOTE

climatic-unit-hfo-mac
Choose item:  
QUOTE FOR MAC+CHILLER
QUOTE FOR ONLY MAC
SERVICE
REPAIR
CALIBRATION
INSPECTION
OTHER REQUEST
Spare parts

Branca hfo Type MAC is the climatic unit designed for big air volumes up to 800 m3

Charged with low gwp refrigerants that enhances a lower energy consumption thanks to its post-heating circuit.

cloud-connect

Here below could be found the advanced features of the close-control unit hfo type MAC:

  • A wide close-control range in presence of critical external environment conditions from -20 up to 40 °C of temperature and 10 to 90 % of Relative humidity;
  • Product certificates CE for EU, UL and CSA for USA and Canada;
  • Modular air flow distribution system with tangential inlet diffusion to the walls mixed with fresh air with inlet speed lower than 0,15 m/s on workdesks;
  • Refrigerant circuit lamination with electronic modulation valves and cooled-water electronic recirculation pump;
  • Reverse osmosis for water treatment and purification to ensure the water supply of demineralized water at 0 °F;
  • Special humidification system with heating elements activated under proportional band;
  • Indoor centrifugal fan with GreenTech technology and analog speed control approved by EU;
  • Prefiltration frontal or from air ducts G3-G4;
  • HMI Touch 7" and PLC for a user-friendly management, monitor and trend graphs, alarms diagnostics and statistics;
  • Remote support control;
  • Reading resolution of probes at 0,01°C and 0,01%;
  • Alarms diagnostics and statistics;
  • Datalogging functions;
  • Normal/ECO operation mode with weekly programming;
  • User manual, guidelines for installation and diagnostics;



INTERNAL LINKS:

Technical data:
Model: MAC
Category: Chilled water unit
Room volume:

climatic-unit-type-mac

(300 ÷ 800) m3
Heating: 13,5 KW
Cooling: 18 KW
Humidification: 12 KW
Refrigerant: Cooled water composition:
50% water
50% Ethylene glycol
Ext. Hydronic module charged with hfo R1234ze

refrigerant-low-gwp
Ventilation: 2,4 KW
Air flow: 6000 m3/h
Motor transmission Coaxial
Air exchange: 1 volume/h
Close-control: (10 ÷ 30) ± 0,5 °C
(40 ÷80) ± 2 %
Water charge: Ø 1/4"
Water discharge: Ø 1/2"
Water discharge connections: Ø 1/2"
Cooled water pipes section: Ø 3 x 16 mm
gwp: < 1
Lubrificant oil: POE, PAG
Power supply: Three phases (3ph+N+PE)
Dimensions (mm): MAC-dimensions
Net weight: 600 Kg
Applications:

The Climatic unit Type MAC is mainly installed in laboratories and environmentally controlled areas aimed to guarantee the quality controls and testing on merceological products.

The main applications are listed below:


textile-testing Textile testing laboratories
Laboratories for fiber classification and testing
Merceological laboratories
Textile products R&D
Textile products quality control
Physical and mechanical testing labs
metrological-rooms
precision-mechanics
Metrological rooms and various laboratory for Metrology as:
Dimensional Metrology
Three-dimensional metrology and CMM (Coordinate Measuring Machines)
Roundness
Electrical Metrology
Metrology of the masses
Metrology of the volumes
Metrology of the forces
Laboratories for Metrology
Laboratories for Precision Mechanics
Automotive e Racing
Aerospatial
Defence
Altro..
paper-testing-laboratories Paper testing laboratories
Technical compression and stacking tests on corrugated cardboard and cardboard boxes
Technical compression, flexure, rigidity tests on paper, board and corrugated board samples, small plastic containers, bottles;
Short span compression strength tests on fluting and liner
Tensile strength and stretch of samples of paper and cardboard according to the standard EN ISO 1924-2 for paper and cardboard and PrEN 12624-4 for tissue;
timing-facilities Precise Timing Facility (PTF)
Altro..
concrete-testing-laboratories Laboratories for Cements testing
Maturation of concrete specimens
Gelivity testing on concrete
Others
adhesives-glues-testing Adhesive and Glues testing laboratories
Tapes testing laboratories
Others.
Photogallery:
  • hydronic-module
  • branca-cloud-connect